Ventilation boxes
SELECTION
CURVES VIRTUO N° 7_9_10_12
Static pressure in Pa
Air filters pressure drop VIRTUO N° 7
Air pressure drop in Pa
3/h x 1000
VIRTUO N° 9
VIRTUO N° 10
VIRTUO N° 12
te Fil
rG
Fi
4
lte
rG
Fi
Fil
4
lte
ter
rG
G4
4
3/h x 1000 Static pressure in Pa
VIRTUO N° 35
VIRTUO N° 45
VIRTUO N° 56
rpm
rpm
rpm
Fil
G ter
4
Filte
r G4
Filt
er
G4
3/h x 1000
Selection example: For air flow of 9,000 m3/h and Static pressure (Pa) 200 Pa Transfer the desired air flow rate (m3/h x 1,000) to the flow rate scale Transfer the static pressure value (Pa) to the pressure scale. The intersection of the flow rate and pressure lines produces a point X. This point X provides the following information: The turbine rotation speed - 790 rpm in our example The sound pressure - 55 dB in our example The power input - 2.0 kW in our example To define the motor power required for your installation, select a motor with a power reserve of 10 to 20%.
Static pressure : pressure level in dB(A) measured at 5 m in a room with average reverberation. Intake and discharge outlets connected. Precision ±3 dB(A). To obtain the power level, add 15 dB to the values written on the curves.