Roof top
Humidity Temperature Thermal and acoustic insulation (50 mm thick), with Euroclass A2-s1, d0 (M0) fire classification. Casing losses:
Conditions Indoor Outdoor 9 mm NBR (std) Winter 20ºC -20ºC 50% RH 94% RH
Droplet eliminator on the indoor air coil (optional on models 415 to 960, and included on models 1100 and 1200). Recommended if high levels of air humidity are expected or when the air flow speed is high. Droplet eliminator on the outdoor air intake. Tropicalised components on the electric panel with protective varnish: control board, card and terminals. Tropicalised fans and motors (please contact us). Indoor separator
1790 W 2.0% HC 0.4% HC
50 mm mineral wool 437 W Conditions Indoor Outdoor 9 mm NBR (std)
Summer 27ºC 35ºC 50% RH 40% RH
615 W 1.00% HC
50 mm mineral wool 151 W 0.24% HC
Hot water auxiliary coil, with three-way valve. This optional always incorporates an anti-freeze thermostat as safety system. Consult for percentages of glycol water above 20%. Auxiliary electrical heaters, with two power stages and on/ off control, for assembly and connection inside the unit. Note: the differential pressostat for control of air flow is included with centrifugal fan (optional). Natural or propane gas burner with modulating actuator. Available for all the models, except 415 and 480. Available for all the assemblies wtih lateral supply. With this option, it is recommended to have the differential pressostat option for detecting clogged filters. Note: with centrifugal fan (optional) and gas burner, it is compulsory the differential pressostat for controlling the air flow that stops the burner in case of fire. Note: a protection kit of low temperature is available for an outdoor temperature lower than -15ºC.
Electrical heater to protect the components of the electrical cabinet. Compulsory if the outdoor temperature is below -8ºC WB. For temperatures below -16ºC WB, a reinforced heater will be compulsory. Compressor with protection against low temperatures (additional crankcase heater): compulsory if the outdoor temperature is below -8ºC WB. Dampers with springs to ensure automatic closure if there is a power outage. Electrical heater for antifreeze protection of the mixing box dampers: compulsory if the outdoor temperature is below -12ºC WB. Hot water coil circuit with antifreeze protection according to the water temperature: compulsory if the outdoor temperature is below -20ºC WB (includes one accelerator pump). Corrosion Coils (outdoor, indoor and/or auxiliary) with copper tubes and copper blades. INERA® coils (outdoor, indoor and/or auxiliary) with copper tubes and aluminium alloy blades, exclusive to CIAT, offering high efficiency and exceptional resistance to corrosion. Coils (outdoor, indoor and/or auxiliary) with copper tubes and aluminium blades, with polyurethane coating or a coil completely protected by Blygold. Stainless steel condensate drain pan for the indoor circuit.
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
533
SPACE PF 415 - 1200