references
TECHNICAL
CHARACTERISTICS
Coil capacity (L)
COADIS LINE 600 2-pipe coil 4-pipe coil Cold water coil Hot water coil 612 0,407 622 0,796 622E 0,608 632 1,212 632E 1,017 0,608 0,231 1,017 0,237 624 634
Diameters of coil couplings
Coil connection type: flush fit female threaded union nuts Valve outlet coupling type: "male" threaded couplings to be used
COADIS LINE 600 2-pipe system 4-pipe system Cold water coil Hot water coil 612 G1/2" G1/2" G1/2" 622 G1/2" G1/2" G1/2" 624 G1/2" G1/2" G1/2" 632 G1/2" G1/2" G1/2" 634 G1/2" G1/2" G1/2"
Motor electrical specifications
COADIS LINE Motor code 612 V5 V4 Input power (W) V3 V2 V1 V5 V4 Input current (A) V3 V2 V1 70 45 41 38 34 0,30 0,21 0,19 0,18 0,17 AC asynchronous motor 622 - 624 70 45 41 38 34 0,30 0,21 0,19 0,18 0,17 632 -634 101 77 56 47 40 0,32 0,29 0,24 0,22 0,21 612 38 17 12 8 5 0,18 0,09 0,07 0,04 0,02 HEE brushless motor 622 - 624 38 17 12 8 5 0,18 0,09 0,07 0,04 0,02 632 -634 56 38 21 15 11 0,40 0,28 0,17 0,13 0,10
Note: Specifications determined for 230V +/-10% - 50Hz supply. For operation at 60Hz, the power input and rotation speed values are generally higher. - Motor operating range: minimum return T°C: 0°C maximum return T°: 40°C
Name plate of the unit
The name plate contains all the information required to identify the unit and its configuration. This plate is positioned on the technical face containing all the connections, above the fresh air inlet. Code Serial number Description of the unit Rated motor output Motor rotation speed Coil type Wiring diagram reference Motor speed wiring Maximum service pressure Electric heater specifications (if fitted)
1 2 3
4
9
5
8
10
6
7
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
341
COADIS LINE 600
4
Comfort units COANDA effect cassette