references
Finned pipes
HEAT
RELEASE
medium and the ambient air temperature. For a given power level, determine the number of the finned pipe and the length (L) needed to dissipate the heat. Pipes are limited to a maximum length of 5.70 metres (4 metres if painted).
Fin pitch 6 26.9 x 2.3 DN 20 8 10 12 8 42.4 x 2.6 DN 32 10 12
Pipe
TA 30 15 16 17 18 40 41 42 43 210 170 146 132 382 321 281 460 402 336 408 343 296 366 386 333 282 477 404 472 488 424 348 727 632 700 608 499 1043 906 743 883 768 1267 1101 924 803 660 1377 1196 983 1673 1234 2100 1826 2214 1160 1009 828 1728 484 730 630 608 917 792 670 737 1112 960 812 719 1407 1223 1004 2096 1822 1496 1769 3011 2616 1187 2478 2871 2496 2049 3488 3033 2846 2338 3979 1663 492 444 773 970 817 40 301 243 210 189 723 608 50 398 322 277 404 348 314 908 763 668 60 70 606 490 421 381 1102 926 810 677 1177 990 800 1390 1170 1010 871 1314 1134 960 1314 1112 984 1927 1170 1010 1736 1499 1268 1123 2198 1910 1767 3689 3206 2632 4482 4998 4342 4801 2476 1689 1429 1410 2761 2399 1970 4114 2178 1297 1302 1094 1267 1109 926 1611 1837 1190 2070 1742 1327 2308 1942 1676 1446 2181 1883 2410 2081 1761 2644 2283 1931 1710 3347 2909 2389 4987 4334 3880 6606 4206 7160 6222 1864 3649 3171 2604 3437 2823 2147 2033 2216 1911 2882 2488 1466 1720 498 80 716 90 829 670 100 946 110 1066 862 741 670 1938 1628 120 1188 961 826 747 2161 130 1313 1063 913 826 2388 2006 140 1440 1166 1002 906 2620 2201 1927 1609 2798 2399 2100 1270 1092 987 150 160 1702
1184 1070 3096 2601 2276 1901 3306 2783 2402 2072 3124 2698 2282 2020
8 48.3 x 2.6 DN 40 10 12
45 46 47 48
10 60.3 x 2.9 DN 50 12
50 51 52
18 12 76.1 x 2.9 DN 65 18 12 88.9 x 3.2 DN 80 18 114.3 x 3.2 DN 100
53 70 71 72 90 91 92 115
18
116
* The values indicated in the table have been obtained in optimal conditions of air circulation around the finned pipes.
Selection example
Heat loss in the room = 2000 W. Available space for finned pipe = 2 metres. Heating water set at 90/70°C with an average temperature of 80°C. Calculation of the necessary power per metre: 2000W / 2m = 1000W/m Thus, for this example, a TA 71 MEME 2000 and two support feet are needed. The power consumption will be 2 x 1009 W = 2018 W.
Stacked finned pipes
Finned pipes may be stacked and connected together with a 3D 180° elbow. See the centre distance figures in the specifications table. When using stacked finned pipes, multiply the heat generated by the following correction factors:
2 3 4
Correction factor
0.92
0.87
0.80
Gutter-mounted finned pipes
Contact us.