references
Split refrigeration units and heat pumps
AIRDUO NEXIA SP/CP - SP/CK
Hot water coil installed inside the unit, with a three-way valve, managed by the control system as back-up heating (heat pump units). The coil air intake temperature is the same as the direct expansion indoor coil output. The three-way valve is supplied in a self-contained kit, for installation on-site outside of the unit.
CP Air pressure drop Heating capacity Water 80/60ºC Water pressure drop Heating capacity Water 90/70ºC Water pressure drop Weight (empty) Diameter of the hydraulic connections (mmWC) (kW) (m3/h) (mWC) (kW) (m3/h) (mmWC) (kg)
90 2.9 12.9 0.6 0.1 17.9 0.8 0.2 7.8
100 3.6 13.7 0.6 0.1 19.2 0.9 0.3 7.8 3/4”
120 4.5 14.9 0.7 0.2 20.8 0.9 0.3 7.8
160 4.2 23.0 1.0 0.5 31.5 1.4 0.8 11.0
182 2.7 30.2 1.3 0.4 41.2 1.8 0.8 16.3
200 3.4 31.6 1.4 0.5 43.5 1.9 0.9 16.3
240 4.0 33.6 1.5 0.5 46.5 2.0 1.0 16.3 1”
280 2.9 44.6 2.0 0.3 61.3 2.7 0.5 34.4
320 3.5 47.4 2.1 0.3 65.4 2.9 0.6 34.4
360 4.1 50.8 2.2 0.4 70.0 3.1 0.7 34.4
- Important: with this option, the air flow controller is included - Standard assembly in 2 stages (for assembly and connection within the unit). - In the case of two indoor units with a single outdoor unit, it is not possible to fit the auxiliary heater in 2 stages (each indoor unit is the equivalent to 1 stage).
Total power (kW) CP Stage power (kW) 90/100/120 Current (A) (400 V/3 PH/50 Hz) Module weight (kg) 160 182/200/240/280/320/360
6 3+3 8.7
9 3+6 13.0
12 6+6 17.3 17.3
15 6+9
18 9+9
24 12 + 12 Unavailable
30 15 + 15
36 18 + 18
Unavailable Unavailable 7.7 9.3
21.7 21.7
26.0 26.0 14.6 34.6 21.4
Unavailable 53.4 25.2 52.0 29.2
10.7
12.6
SP
OUTDOOR UNIT DIMENSIONS
(STANDARD M00
ASSEMBLY)
Dimensions (mm) A 1 191 1 191 1 471 1 471 1 471 2 186 2 746 2 746 2 746 2 746 3 484 3 484 B 860 860 860 860 860 860 860 860 860 860 860 860 C 1 437 1 437 1 717 1 717 1 717 1 427 1 717 1 717 1 717 1 717 1 717 1 717 Weight (kg) 300 315 364 378 383 588 760 775 788 798 832 873
Model outdoor unit RSP/ISP 90 U RSP/ISP 100 U RSP/ISP 120 U RSP/ISP 160 U RSP/ISP 182 U RSP/ISP 200 U RSP/ISP 240 U RSP/ISP 280 U RSP/ISP 320 U
NOTE: dimensions for indoor units (refer to the technical documentation).
RSP/ISP 360 U RSP/ISP 420 U RSP/ISP 485 U
580