references
Inverter Air-Cooled Liquid chillers & Reversible Air to Water Heat Pumps
COOLING
CAPACITIES IN ACCORDANCE WITH
EN14511-3
15
Leaving EREBA Water Cooling Temp. in only °C 5 7 10 15 18 17T 21T 17T 21T 17T 21T 17T 21T 17T 21T
OUTSIDE AIR TEMPERATURE IN °C 5 Pf kW Min 5.4 9.4 5.8 10.0 6.3 10.8 7.3 12.3 7.9 13.3 Pa kW Min 0.5 1.3 0.4 1.3 0.4 1.3 0.4 1.4 0.3 1.4 EER Max 3.1 5.7 3.1 5.7 3.3 5.9 3.5 6.2 3.4 6.6 Nom 5.3 5.3 5.5 5.4 5.7 5.6 6.1 6.6 7.0 7.1 Min 10.8 7.5 13.5 7.8 15.1 8.2 20.5 8.9 25.5 9.3 Max 5.3 4.3 5.5 4.6 5.7 4.9 6.1 5.4 7.0 5.5 Q l/s Nom 0.78 0.99 0.82 1.05 0.89 1.13 1.02 1.34 1.13 1.46 Pf kW Min 5.3 9.0 5.6 9.6 6.2 10.7 7.0 12.5 7.7 13.2 Pa kW Min 0.6 1.6 0.6 1.6 0.5 1.5 0.5 1.4 0.4 1.6 EER Max 3.2 6.2 3.2 6.3 3.4 6.5 3.4 7.0 3.4 7.4 Nom 5.1 4.9 5.2 5.1 5.5 5.5 6.2 6.2 6.9 6.5 Min 9.2 5.8 10.1 6.0 11.9 7.1 13.7 8.6 19.4 8.4 Max 5.1 4.3 5.2 4.4 5.5 4.7 6.2 4.9 6.8 5.1 Q l/s Nom 0.77 0.99 0.81 1.04 0.88 1.15 1.03 1.33 1.13 1.45
Nom 16.3 20.8 17.3 22.0 18.7 23.7 21.2 27.9 23.7 30.5
Max 16.3 24.7 17.3 26.4 18.7 29.0 21.2 33.7 23.7 36.1
Nom 3.1 3.9 3.1 4.0 3.3 4.3 3.5 4.2 3.4 4.3
Nom 16.1 20.7 17.0 21.8 18.5 24.0 21.4 27.8 23.6 30.3
Max 16.1 26.2 17.0 27.9 18.5 30.6 21.4 34.8 23.6 37.5
Nom 3.2 4.2 3.2 4.3 3.4 4.4 3.4 4.5 3.4 4.6
Leaving EREBA Water Cooling Temp. in only °C 5 7 10 15 18 17T 21T 17T 21T 17T 21T 17T 21T 17T 21T
OUTSIDE AIR TEMPERATURE IN °C 25 Pf kW Min 5.6 8.7 6.3 9.3 6.6 10.2 8.1 11.9 8.9 13.0 Pa kW Min 1.1 1.7 1.0 1.8 1.1 1.7 0.9 1.7 0.9 1.7 EER Max 3.6 7.1 3.7 7.3 3.7 7.6 3.9 8.2 4.0 8.5 Nom 4.3 4.2 4.5 4.3 4.8 4.6 5.3 5.0 5.6 5.2 Min 5.1 5.0 6.6 5.3 6.0 5.9 8.7 6.8 10.1 7.5 Max 4.3 3.5 4.5 3.6 4.8 3.7 5.3 3.9 5.6 4.1 Q l/s Nom 0.73 0.95 0.78 1.00 0.85 1.09 0.98 1.26 1.07 1.36 Pf kW Min 5.8 9.3 6.3 9.9 7.0 10.8 8.2 12.5 9.0 13.6 Pa kW Min 1.6 2.5 1.6 2.5 1.6 2.6 1.6 2.6 1.5 2.6 35 EER Max 5.0 8.5 5.1 8.7 5.3 9.1 5.6 9.7 5.8 10.1 Nom 3.2 3.2 3.5 3.3 3.6 3.5 3.9 3.9 4.3 4.1 Min 3.6 3.7 3.9 3.9 4.3 4.2 5.2 4.8 5.9 5.2 Max 3.1 2.8 3.2 2.8 3.4 3.0 3.7 3.2 3.9 3.3 Q l/s Nom 0.70 0.86 0.76 0.91 0.82 1.00 0.94 1.15 1.06 1.24
Nom 15.4 19.8 16.3 21.0 17.8 22.9 20.5 26.2 22.2 28.3
Max 15.4 24.6 16.3 26.0 17.8 28.3 20.5 32.2 22.2 34.7
Nom 3.6 4.8 3.7 4.9 3.7 5.0 3.9 5.3 4.0 5.5
Nom 14.7 18.1 16.0 19.2 17.1 21.0 19.6 24.1 22.2 25.9
Max 15.8 23.5 16.7 24.9 18.2 27.0 20.9 30.8 22.6 33.3
Nom 4.5 5.6 4.6 5.8 4.8 5.9 5.0 6.2 5.2 6.3
Leaving EREBA Water Cooling Temp. in only °C 5 7 10 15 18 17T 21T 17T 21T 17T 21T 17T 21T 17T 21T
OUTSIDE AIR TEMPERATURE IN °C 45 Pf kW Min 7.8 9.0 8.4 9.6 9.2 10.5 10.7 12.2 11.7 13.3 Pa kW Min 3.0 3.6 3.1 3.6 3.1 3.7 3.2 3.8 3.2 3.9 EER Max 5.2 7.3 5.3 7.4 5.5 7.7 5.8 8.1 5.9 8.4 Nom 2.5 2.5 2.6 2.6 2.8 2.7 3.1 3.0 3.2 3.1 Min 2.6 2.5 2.7 2.6 2.9 2.9 3.4 3.2 3.6 3.4 Max 2.5 2.4 2.6 2.5 2.8 2.6 3.1 2.9 3.2 3.0 Q l/s Nom 0.63 0.77 0.67 0.82 0.73 0.90 0.84 1.04 0.92 1.13
Nom 13.2 16.2 14.0 17.2 15.3 18.8 17.6 21.7 19.1 23.5
Max 13.2 17.4 14.0 18.5 15.3 20.2 17.6 23.3 19.1 25.2
Nom 5.2 6.6 5.3 6.7 5.5 6.9 5.7 7.3 5.9 7.5
Entering/leaving water temperature difference : 5K Fouling factor : 0 m² K/W Pure water fluid Performances in accordance with EN14511-3:2011
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
37
Ereba 17-21
Ereba cooling only