references
Condensing units
QUICK
28 35 50 65 75
SELECTION
Number of circuits 1 1 1 1 1 Number of compressors 1 1 1 1 1 Cooling capacity (kW) 6.8 8.6 12.1 14.5 18.6 Power consumption (kW) 2.6 3.5 4 4.9 6.8
CONDENCIAT CL2
CONDENCIAT CL2
CL2 refrigerant fluid R410A Evaporation temperature + 2 °C DB air temperature at condenser = + 35 °C
DIMENSIONS
Models 28 and 35 Models 50, 65 and 75
350 5 350
350
5
350 1305 600
377,5 45
705
Option Anti-vibration mounts
27
Anti-vibration mount spacing
27
Anti-vibration mount spacing
100 263 602 1035
100 170
Option Anti-vibration mounts
377,5 45
Anti-vibration mount spacing
100 263 602 1035
100 170
Anti-vibration mount spacing
410 450
410 450
CONNECTION
r orato Evap
R
x
Max height 30 m Max equivalent length 50 m Max height 30 m Max equivalent length 50 m
r orato Evap
Equivalent length for 90° angle:
Tube diameter (inches) Equivalent length (m) 1/4” 0.25 3/8” 0.35 1/2” 0.45 5/8” 0.55 3/4” 0.65 7/8” 0.7
All the network accessories must be taken into account. 287
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
CONDENCIAT CL2