Centrifugal air heaters hot water or electrical supply
SILENTHERME
ELECTRICAL SILENTHERME
Selection tables - Air flow rate / Heating capacity Temperature + 12 °C at inlet
3/h
Series
Silentherme 15
ES and S
GV and TGV
Power* kW 6
Number of stages 1 1 2 1 1 2 1 1 2 1 1 2 1 1 2
Resistances Unit power kW 2 2 2 3 3 3 3 3 3 4 4 4 5 5 5 Number 3 6 6 3 6 6 6 9 9 6 12 12 6 12 12
1
16 17 25
400 to 1800
1000 to 3300
12 12 (6 + 6) 9
2
26 27 35
1000 to 2700
1600 to 5200
18 18 (9 + 9) 18
3
36 37 45
1600 to 4200
2400 to7800
27 27 (9 + 18) 24
4
46 47 55
2600 to 5700
3500 to 10500
48 48 (12 + 36) 30
5
56 57
3600 to 7500
5000 to 14000
60 60 (15 + 45)
* Power based on average values indicated by suppliers of electrical resistances. P in kW x 860 Q in m3/h x 0,3
Example of selection
3/h depending upon your requirements.
Connection diagram
SG: FV: KV: Main isolating switch Fan fused isolator Fan switch
INT: Fan / Off / Heat switch
FTV: Thermal relay MV: Fan motor PT: FR: KR: BR: Thermal protection of motor (TPO) or PTC (TPO option) Heating elements cut-off fuse Heating elements switch Sets of heating elements safety thermostat Th: K1: Room thermostat Timer relay Supplied by CIAT
BSC: Manual reset
NOTE: this is a block diagram only ; the earth circuit connections are not shown but must nevertheless be implemented. If the fan is fitted with a two speed motor, the regulation system must ensure that a reduction in the air flow rate immediately leads to a proportional reduction in the battery power :
Caution: the surge current and the resultant rating of the protective devices must be calculated by the installer depending on the supply voltage on the site. installer). Provide a 3 to 5 minute time delay on the fan to cool the heater coil. (top to bottom).
At low speed, the power dissipated by the heater coil must not exceed 30 kW.