references
Roof top
SPACE PF 415 - 1200
MRC cooling recovery circuit
Space PF (m3/h) Available static pressure EC plug-fan (MRC0 / MRC1) in return Centrifugal fan (MRC1) Maximum available static pressure in return Extra weight (mm.w.c) (mm.w.c) (kg) 415 420 480 485 540 600 650 720 840 960 1100 1200
18.000 18.000 18.200 18.200 20.400 24.000 27.500 30.000 33.000 37.000 42.000 46.000 45,3 12,5 -17 49,1 12,5 -16 43,1 15,0 -17 47,0 15,0 -16 77,8 15,0 -34 63,6 15,0 -27 1/1 Copeland 3MAF 32cST, Danfoss POE 160SZ, ICI Emkarate RL 32CF, Mobil EAL Artic 22CC 3,0 15,3 8,0 8,0 8,0 8,0 8,1 3,3 20,1 8,2 7,6 4 25,1 7,7 7,1 6,2 30,5 7,1 8,2 6,2 39,8 8,2 40,7 17,5 -15 68,2 17,5 -44 56,8 17,5 2 38,3 17,5 2 94,1 17,5 96 77,8 17,5 96
No. of compressors / circuits Recovery Oil type scroll compressor Volume of oil (l) characteristics Max. absorbed current (A) Refrigerant charge R-410A (kg)
Important : With this option, CIATrtc electronic control is mandatory, the change of control isn’t allowed.
MRC00 assembly MRC11 assembly
SPACE PF Air pressure drop Water 80/60ºC and air intake 20ºC Water 90/70ºC and air intake 20ºC Weight (empty) Heating capacity Water pressure drop Heating capacity Water pressure drop (mmWC) (kW) (m3/h) (mWC) (kW) (m3/h) (mWC) (kg)
415 2.7 146.3 6.5 1.7 179.8 8.0 2.6 43.0
420 2.1 181.2 8.0 2.0 223.1 9.9 2.4 66.9
480 2.7 147.3 6.5 1.8 181.1 8.0 2.6 43.0
485 2.1 182.5 8.1 2.0 224.7 10.0 2.5 66.9
540 2.5 196.0 8.7 1.9 241.5 10.7 2.8 66.9
600 3.3 216.3 9.2 2.3 266.9 11.9 3.5 66.9
650 2.9 255.0 11.3 3.1 314.5 14.0 3.9 82.3
720 3.4 268.7 11.9 3.4 331.6 14.7 4.3 82.3
840 4.0 284.3 12.6 3.8 351.0 15.6 4.8 82.3
960 4.8 303.8 13.5 4.4 375.3 16.7 5.5 82.3
1100 4.5 326.7 14.4 2.1 403.3 17.9 3.2 82.3
1200 5.3 352.4 15.6 2.4 436.6 19.3 3.7 82.3
Note: with a droplet eliminator on the indoor air coil, it is not possible to fit a hot water coil. This option still includes a built-in antifreeze thermostat to protect the coil.
Position of the auxiliary hot water coil hydraulic connections (option)
SPACE PF 415 / 420 / 480 / 485 / 540 / 600 650 / 720 / 840 / 960 1100 / 1200
A (mm) 302 302 302
B (mm) 250 250 250
C (mm) 222 222 222
Ø of hydraulic connections: I/O 2” 2” 2 1/2”
KEY
1 2
Water outlet Water inlet
Note: the inlet/outlet connections for the coil are located within the unit. The connection can be made at the base of the unit, using the flexible sleeves, or via the lateral panel. The diagram above shows the location of the pre-punched holes located on the lateral panel. For connections via the base, consult the plans for the pre-assembled frames.
540