Compact air-air rooftop units
PJ range
TECHNICAL
PJ range Cooling capacity Cooling capacities Power input (kW)
CHARACTERISTICS (EN-14511-2013)
0090
22.5 7.3 3.10
0120
28.3 9.4 3.01 28.1 8.0 3.50
0140
34.7 11.0 3.16 33.7 9.6 3.53
0160
38.6 12.6 3.06 38.2 10.9 3.50
0180
42.9 14.2 3.01 42.4 12.3 3.44
0190
45.5 15.1 3.01 45.3 13.3 3.41
0200
53.1 17.2 3.09 51.5 15.0 3.44
0220
57.7 19.1 3.03 56.7 16.6 3.42
0240
60.3 20.1 3.01 59.5 17.4 3.41
0280
67.7 21.9 3.09 67.9 19.5 3.49
0320
71.3 23.4 3.05 72.2 20.9 3.45
0360
80.2 26.4 3.04 80.8 23.6 3.43
0380
90.0 29.9 3.01 90.9 26.7 3.41
(kW)
EER performance Heating capacity Heating capacities Power input (kW) (kW)
22.0 6.0 3.67
COP performance
3
/h)
9 000 14 500 17 000 17 000 17 000 17 750 31 000 31 000 31 000 33 000 33 000 34 500 35 000 5 Electronic axial fan 1 / 630 0.9 1 140 5 100 12 6 500 12 8 700 12 1 / 800 2.6 1 020 9 250 15 9 450 15 2 / 800 2 x 2.6 1 020 9 450 12 000 12 500 12 500 16 000 16 000 16 500 16 500 15 20 20 20 20 20 25 25
Available static pressure (mm.w.c) Outdoor circuit fan Type Number / Diameter (mm) Motor output (kW)
Maximum speed (r.p.m.)
3
/h)
Available static pressure (mm.w.c) Indoor circuit supply air fan Type Number / Diameter (mm) Motor output (kW) Speed (r.p.m.) Type Compressor No. compressors / stages / circuits Oil type Volume of oil (l) Mains voltage Electrical characteristics Power supply Maximum absorbed current (A) Type Refrigerant Global warming potential (GWP) Charge (kg) Environment impact (tCO2eq) Weight C0 assembly (kg)
Electronic plug-fan 1 / 500 1 x 2.65 2 x 2.65 1 700 Scroll 2/2/1 4/4/2 2 / 500 1 x 2.83
Copeland 3MAF 32cST, Danfoss POE 160SZ, ICI Emkarate RL 32CF, Mobil EAL Artic 22CC 2.5 2.5 3.3 3.5 3.5 3.5 5.0 5.0 5.8 6.6 6.9 7.1 7.1
400 V / III ph / 50 Hz (±10%) 3 Wires + Ground + Neutral 18.5 26.5 30.5 33.5 37.5 38 44.3 R-410A 2.088 6.7 14.0 585 7.0 14.6 610 11.0 23.0 675 11.0 23.0 680 11.5 24.0 685 11.5 24.0 690 12.5 26.1 990 12.5 26.1 995 13.0 27.1 1.040 19.5 40.7 1.155 19.5 40.7 1.160 20.0 41.8 1.165 20.0 41.8 1.170 49.9 50.1 50.2 53.7 62.3 67.5
Cooling capacity calculated in accordance with the EN-14511-2013 standard given for indoor temperature conditions 27ºC, 19ºC WB and 35ºC outdoor temperature. Heating capacity calculated in accordance with the EN-14511-2013 standard given for indoor temperature conditions 20ºC and 6ºC WB outdoor temperature. Total power input by compressors and motorised fans under nominal conditions, calculated in accordance with the EN-14511-2013 standard. Climatic warming potential of a kilogram of fluorinated greenhouse gas in relation to a kilogram of carbon dioxide over a period of 100 years.
OPERATION
Inlet air conditions Indoor coil
LIMITS
Cooling Minimum Maximum Minimum Maximum 13ºC WB 24ºC WB 12ºC 48ºC Heating 10ºC 27ºC -15ºC WB 15ºC WB
With a condensation pressure control operating down to -10ºC. When the outdoor temperature is usually below 5ºC WB the installation of a support element is recommended.
Outdoor coil