references
Inverter Air-Cooled Liquid chillers & Reversible Air to Water Heat Pumps
Ereba 17-21
COOLING
CAPACITIES IN ACCORDANCE WITH
EN14511-3
15
Ereba reversible
Leaving EREBA Water ReversTemp. in ible °C 5 7 10 15 18 17HT 21HT 17HT 21HT 17HT 21HT 17HT 21HT 17HT 21HT OUTSIDE AIR TEMPERATURE IN °C 5 Pf kW Min 13.3 14.4 14.1 15.2 7.9 16.5 8.5 18.8 9.1 20.3 Pa kW Min 2.7 3.0 2.7 3.0 1.1 3.1 1.1 3.2 1.2 3.3 EER Max 3.0 6.3 3.0 6.3 3.2 6.4 3.4 6.7 3.5 6.9 Nom 5.3 5.0 5.5 5.1 5.7 5.2 6.1 5.8 6.3 6.0 Min 5.0 4.9 5.2 5.1 7.6 5.4 7.7 5.9 7.9 6.2 Max 5.3 3.9 5.5 4.2 5.7 4.6 6.1 5.0 6.3 5.3 Q l/s Nom 0.75 1.00 0.79 1.05 0.86 1.14 0.99 1.32 1.06 1.41 Pf kW Min 9.9 12.8 10.5 13.5 6.2 8.1 7.0 9.5 7.1 9.9 Pa kW Min 1.7 3.9 1.7 4.0 0.7 1.7 0.7 1.6 0.8 1.8 EER Max 3.4 6.3 3.5 6.4 3.6 6.5 3.8 6.8 4.0 7.0 Nom 4.5 4.6 4.6 4.7 4.9 4.9 5.3 5.7 5.5 6.1 Min 5.7 3.3 6.4 3.4 9.4 4.8 9.3 6.0 9.3 5.6 Max 4.5 3.9 4.6 4.1 4.9 4.4 5.3 4.9 5.5 5.2 Q l/s Nom 0.73 0.98 0.78 1.03 0.85 1.12 0.98 1.31 1.06 1.43
Nom 15.7 20.9 16.6 22.0 18.0 23.8 20.6 27.5 22.2 29.5
Max 15.7 24.5 16.6 26.4 18.0 29.0 20.6 33.3 22.2 36.3
Nom 3.0 4.2 3.0 4.4 3.2 4.6 3.4 4.7 3.5 5.0
Nom 15.4 20.5 16.3 21.6 17.8 23.3 20.4 27.3 22.0 29.8
Max 15.4 24.5 16.3 26.3 17.8 28.7 20.4 33.3 22.0 36.3
Nom 3.4 4.4 3.5 4.6 3.6 4.8 3.8 4.8 4.0 4.9
Leaving EREBA Water ReversTemp. in ible °C 5 7 10 15 18 17HT 21HT 17HT 21HT 17HT 21HT 17HT 21HT 17HT 21HT
OUTSIDE AIR TEMPERATURE IN °C 25 Pf kW Min 9.0 13.8 9.6 14.7 5.2 8.4 6.1 9.8 7.0 10.8 Pa kW Min 2.0 3.2 2.0 3.3 1.2 1.9 1.1 1.9 0.9 1.8 EER Max 3.8 6.9 3.8 7.1 3.9 7.4 4.0 7.9 4.2 8.2 Nom 3.9 4.1 4.1 4.2 4.4 4.4 4.9 4.8 5.2 5.0 Min 4.4 4.3 4.7 4.5 4.6 4.4 5.4 5.2 7.8 5.9 Max 3.9 3.5 4.1 3.6 4.4 3.7 4.9 3.9 5.2 4.0 Q l/s Nom 0.69 0.95 0.75 1.01 0.82 1.10 0.95 1.26 1.03 1.36 Pf kW Min 3.0 8.3 3.2 8.9 3.6 9.7 4.2 11.2 4.6 12.2 Pa kW Min 1.3 2.5 1.3 2.5 1.3 2.7 1.2 2.7 1.2 2.8 35 EER Max 5.0 8.3 5.1 8.5 5.3 8.8 5.6 9.4 5.6 9.8 Nom 3.0 3.1 3.1 3.2 3.4 3.2 3.7 3.5 4.0 4.0 Min 2.3 3.3 2.5 3.5 2.8 3.6 3.4 4.1 3.9 4.4 Max 3.0 2.7 3.1 2.8 3.3 2.9 3.6 3.1 3.8 3.2 Q l/s Nom 0.68 0.86 0.73 0.91 0.79 1.00 0.92 1.15 1.03 1.26
Nom 14.5 19.9 15.6 21.1 17.1 22.9 19.8 26.2 21.5 28.3
Max 14.5 23.8 15.6 25.2 17.1 27.3 19.8 31.0 21.9 33.3
Nom 3.8 4.9 3.8 5.0 3.9 5.2 4.0 5.4 4.1 5.6
Nom 14.3 18.1 15.2 19.1 16.6 20.9 19.2 23.9 21.4 26.4
Max 14.8 22.3 15.8 23.6 17.3 25.6 19.9 29.1 21.6 31.3
Nom 4.7 5.8 4.8 6.0 5.0 6.4 5.2 6.8 5.4 6.6
Leaving EREBA Water ReversTemp. in ible °C 5 7 10 15 18 17HT 21HT 17HT 21HT 17HT 21HT 17HT 21HT 17HT 21HT
OUTSIDE AIR TEMPERATURE IN °C 45 Pf kW Min 4.0 6.5 4.2 6.9 4.7 7.6 5.4 8.8 5.9 9.6 Pa kW Min 2.7 2.8 2.8 2.8 2.8 2.9 2.9 3.0 2.9 3.0 EER Max 5.2 7.1 5.3 7.2 5.5 7.5 5.8 7.9 5.9 8.1 Nom 2.4 2.4 2.5 2.5 2.6 2.6 2.9 2.8 3.1 3.0 Min 1.4 2.3 1.5 2.4 1.7 2.6 1.9 3.0 2.0 3.2 Max 2.4 2.3 2.5 2.4 2.6 2.6 2.9 2.8 3.1 2.9 Q l/s Nom 0.58 0.72 0.62 0.77 0.69 0.84 0.80 0.97 0.89 1.05
Nom 12.3 15.2 13.1 16.1 14.3 17.6 16.7 20.2 18.5 21.9
Max 12.3 16.4 13.1 17.4 14.4 19.0 16.7 21.8 18.5 23.6
Nom 5.2 6.4 5.3 6.6 5.5 6.8 5.8 7.1 5.9 7.3
Entering/leaving water temperature difference : 5K Fouling factor : 0 m² K/W Pure water fluid Performances in accordance with EN14511-3:2011
36
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A