references
Split refrigeration units and heat pumps
RST/IST Cooling capacity Cooling capacities Power input (kW) EER performance Heating capacity Heating capacities Power input (kW) 3/h) Available static pressure (mm.w.c) Outdoor circuit centrifugal fan Number / turbines Motor output (kW) Power input (kW) Speed (r.p.m.) Type Compressor No. compressors / circuits / stages Oil type Volume of oil (l) Cooling connections Liquid line Gas line Type Refrigerant Global warming potential (GWP) Load up to 7,5 m (kg) Environment impact (tCO2 e) Electrical features Mains voltage Power supply Compressor (A) Maximum absorbed current Fan (A) Control (A) Total (A) Length (mm) Dimensions Width (mm) Height (mm) Weight (kg) RCT/ICT 3/h) Available static pressure (mm.w.c) Indoor circuit centrifugal fan Number / turbines Motor output (kW) Power input (kW) Speed (r.p.m.) Max. abs.current Fan (A) Length (mm) Dimensions Width (mm) Height (mm) Weight (kg) COP performance (kW) (kW)
80
19.3 8.0 2.40 22.3 7.7 2.88 6 500 25
90
21.2 9.6 2.20 24.2 9.1 2.67 7 000 20 1/1
120
27.3 11.5 2.38 32.0 10.6 3.03 10 000 20
160
36.9 14.2 2.60 41.9 13.5 3.11 12 200 20
3 2.33 1 489
3 2.71 1 522 Scroll 1/1
4 2.51 940
5.5 3.18 836
Copeland 3MAF 32 cST, Danfoss POE 160 SZ, ICI Emkarate RL32 CF, Mobil EAL Artic 22 CC 1.6 1/2" 7/8" 3.0 1/2" 7/8" R-410A 2 088 6.5 13.6 6.6 13.8 7.8 16.3 10.2 21.3 3.3 5/8" 1 1/8" 3.3 5/8" 1 1/8"
400 V / III ph / 50 Hz (±10%) 3 Wires + GND 15.9 6.9 0.9 23.7 1 680 915 670 224 15.3 6.9 0.9 23.1 1 680 915 670 245 20.1 9.0 0.9 30.0 2 088 1 198 810 322 25.1 11.6 0.9 37.6 2 088 1 198 810 344
80
4 000 20
90
4 600 20 1/1
120
6 000 20
160
7 000 20
1.5 1.07 1 497 3.6 1 500 870 639 125
2.2 1.48 1 613 5.0 1 500 870 639 128
2.2 1.56 1 219 5.0 1 831 1 103 706 171
2.2 1.62 1 030 5.0 1 831 1 103 706 181
Cooling capacity calculated in accordance with the EN-14511-2013 standard given for indoor temperature conditions 27ºC (19ºC WB) and 35ºC outdoor temperature. Heating capacity calculated in accordance with the EN-14511-2013 standard given for indoor temperature conditions 20ºC and 6ºC WB outdoor temperature. Total power input by compressors and motorised fans under nominal conditions, calculated in accordance with the EN-14511-2013 standard. period of 100 years.
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
585