references
Compact air-to-air packaged units
TECHNICAL
CHARACTERISTICS
HCompact2 HA 55 (kW)
12.5 5.2 2.38
65
15.3 6.6 2.30 16.9 5.7 2.96 4 600 9
80
20.1 7.4 2.70 21.1 6.4 3.29 6 500 10 Centrifugal 1
90
21.5 8.5 2.53 23.1 7.4 3.13 7 000 10
120
27.1 11.0 2.47 30.5 9.3 3.28 10 000 12
160
35.9 15.4 2.33 41.0 13.3 3.10 12 200 12
Cooling capacity Cooling capacities Power input (kW)
EER performance Heating capacity Heating capacity Power input (kW) 3/h) Available static pressure (mm w c) Outdoor circuit fan Type Number Motor output (kW) Power input (kW) Speed (r p m ) 3/h) Available static pressure (mm w c) Indoor circuit fan Type Number Motor output (kW) Power input (kW) Speed (r p m ) Type Compresor number Compressor Circuit number Oil type Voulme of oil (l) Electrical characteristics Electrical power supply Power supply Compressor (A) Maximum absorbed current Outdoor fan (A) Indoor fan (A) Control (A) Total (A) Type Refrigerant Global warming potential (GWP) Charge (kg) Environment impact (t CO2e) Length (mm) Dimensions Width (mm) Height (mm) Weight (kg) (kW)
14.2 4.8 2.93 4 100 9
COP performance
1.1 0.77 1 125 2 500 5.0
1.5 1.01 1 207 3 100 5.0
1.5 1.14 828 4 000 6.2 Centrifugal 1
2.2 1.33 859 4 600 6.2
2.2 1.37 589 6 000 6.2
3.0 2.03 630 7 000 7.5
0.55 0.35 1 115
1.1 0.63 1 340
1.1 0.67 1 051 Scroll 1 1
1.5 0.94 1 150
1.5 1.20 988
3.0 1.94 1 168
Copeland 3MAF 32cST, Danfoss POE 160SZ, ICI Emkarate RL 32CF, Mobil EAL Artic 22CC 1.6 1.6 1.6 3.0 3.3 3.3
400 V / III ph / 50 Hz (±10%) 3 Wires + Ground 15.0 2.7 1.6 2.0 21.3 19.0 3.6 2.7 2.0 27.3 19.0 3.6 2.7 2.0 27.3 R-410A 2 088 2.5 5.2 1 420 1 065 576 245 3.0 6.3 1 420 1 065 576 253 4.5 9.4 1 760 1 414 701 332 3/4” 4.9 10.2 1 760 1 414 701 375 5.0 10.4 2 300 1 820 824 472 6.2 12.9 2 300 1 820 824 521 22.0 5.0 3.6 2.0 32.6 29.0 5.0 3.6 2.0 39.6 35.0 6.9 6.9 2.0 50.8
Ø Condensate evacuation
Cooling capacity calculated in accordance with the EN-14511-2013 standard given for indoor temperature conditions 27ºC, 50% RH and 35ºC outdoor temperature. Heating capacity calculated in accordance with the EN-14511-2013 standard given for indoor temperature conditions 20ºC and 6ºC WB outdoor temperature. Total power input by compressor and motorised fans under nominal conditions calculated in accordance with the EN-14511-2013.
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
593
HCOMPACT2 HA