references
Compact air-to-air packaged units
POWER
LEVEL AND SOUND PRESSURE LEVEL DB(A)
80
74,4 79,4 65,7
VCompact NE dB(A) dB(A) dB(A)
90
76,3 75,1 67,9
120
81,9 77,5 71,4
160
83,6 80,2 74,0
180
79,3 77,8 70,8
240
84,9 83,1 75,2
320
86,6 79,0 76,0
A) The sound power level in the outdoor fan to be taken into account for the silencer calculation. B) The sound power level in the indoor fan to be taken into account for the silencer calculation. C) The sound pressure level of the unit, with the return and outlet connections ducted, measured at a distance of 5 meters, in open field, the directivity at 2 and 1.5 meters from the earth. Note: The sound pressure level depends on the installation conditions and, as such, it only indicated as a guide.
ELECTRICAL
HEATER (OPTION)
Important: with this option, the air flow controller is included. Electric heater assembly in 1 stage, except for 24 kW to 36 kW with assembly in 2 stages. For another stages configuration, it is necessary to check if it is possible and the price.
VCompact NE 80 / 90 / 120 / 160 180 / 240 / 320
Power supply Power output (kW) Current (A) Current (A) 3
4,3 4,3
400 V / III ph / 50 Hz 6
8,7 8,7
9
13 13
12
17,3 17,3
15
21,7 21,7
18
26 26
24
30
unavailable
36
34,6
43,4
52,0
Note: in models with centrifugal return fan it is to check available power output.
A
Dimensions (mm) VCompact NE Power output A 3 to 6 kW (1 row) 80 (1 supply outlet) 9 to 12 kW (2 rows) 15 to 18 kW (2 rows) 90 (1 supply outlet) 120 / 160 (1 supply outlet) 180 / 240 (2 supply outlets) 320 (2 supply outlets) 3 to 9 kW (1 row) 12 to 18 kW (2 rows) 3 to 12 kW (1 row) 15 to 18 kW (2 rows) 3 to 18 kW (1 row) 24 to 36 kW (2 rows) 3 to 18 kW (1 row) 24 to 36 kW (2 rows)
150 262 262 150 262 150 262 150 262 150 262
B
432 432 482 482 482 432 432 482 482 547 547
C
341 341 443 443 443 341 341 443 443 443 443
C
B
This frame is designed with side access for maintenance purposes. In models with two supply outlet (two frames), the electrical heaters are distributed as symmetrically as possible between both frames.
AUXILIARY
HOT WATER COILS (OPTION)
VCompact NE (m3/h) 80
4.000 33 3,7 1,0 1 1/4”
Two-row hot water coils for mounting in duct, except for 120 and 160 models for mounting inside of the unit
90
4.600 35 4,6 1,2 1 1/4”
120
6.000 51 3,5 1,2 1 1/2”
160
7.000 56 4,5 1,4 1 1/2”
180
9.200 74 4,6 1,2 1 1/2”
240
12.000 103 3,5 1,4 2”
320
14.000 112 4,5 1,6 2”
Heating capacity (water 80/60ºC and inlet air 21ºC) (kW) Air pressure drop Water pressure drop Hidraulic connections: I/O (mm.w.c.) (m.w.c.)
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
599
VCOMPACT NE