references
QUICK
SELECTION
GeoCIAT Modular 20H kW kW 5,42 1,26 4,3 kW kW 5,16 1,54 3,35 kW kW 7,15 1,26 5,68 kW kW 6,81 1,54 4,43 33H 7,04 1,6 4,4 6,7 1,95 3,43 9,29 1,6 5,81 8,84 1,95 4,53 45H 9,79 2,33 4,2 9,31 2,84 3,28 12,92 2,33 5,54 12,29 2,84 4,33 45HT 9,78 2,15 4,55 9,31 2,62 3,55 12,91 2,15 6 12,29 2,62 4,68
Heating capacity at 0/-3°C 30/35°C* Power input * COP* Heating capacity at 0/-3°C 40/45°C* Power input * COP* Heating capacity at 10/7°C 30/35°C Power input COP Heating capacity at 10/7°C 40/45°C Power input COP Power supply Sound power*
* NFPAC certified values under no. NF 414-1385E/1068.
230V - 1ph - 50Hz + E + N dB(A) 48 49
400V - 3ph - 50Hz + E + N 50 50
WATER
FLOW RATE
IMPORTANT: The minimum flow rates must be observed. If they are not, the exchanger may be damaged by frost. CIAT shall not be held liable for frost which results from flow rates below the minimum flow rates stated above. The nominal flow rates are used to size the hydraulic system.
GeoCIAT Modular
3
20H 0,7
3 3
33H 0,85 1,7 2,4 0,65 1,3
45H 1,2 2,4 3,3 0,85 1,7
45HT 1,2 2,4 3,3 0,85 1,7
Outdoor heat exchanger Indoor heat exchanger
(1) (2)
/h) /h) (1)
1,4 1,9 0,5
/h)
(2)
3
/h)
3
/h)
1
0/-3°C // 30/35°C mode 10/7°C // 30/35°C mode
HYDRAULIC
CONNECTIONS
System pipe diameters calculated for a hydraulic connection for your machine of 15m between the unit and the rest of the system.
GeoCIAT Modular
Hydraulic connection copper tubing 28 x 1 28 x 1 32 x 1 32 x 1
Hydraulic connection steel tubing 33/42 - DN32 1’’ 1/4 33/42 - DN32 1’’ 1/4 33/42 - DN32 1’’ 1/4 33/42 - DN32 1’’ 1/4
Hydraulic connection PE tubing 32 x 2.9 32 x 2.9 40 x 3.7 40 x 3.7
20H 33H 45H 45HT
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
203
GeoCIAT™ Modular
2
Heat pump Heating only, Glycol/water mix/water