references
TECHNICAL
CHARACTERISTICS
Motor electrical specifications
COADIS LINE 900 Motor code V5 V4 V3 V2 V1 V5 V4 V3 V2 V1 AC asynchronous motor 922 102 89 69 53 35 0.44 0.39 0.30 0.23 0.15 932 102 89 69 53 35 0.44 0.39 0.30 0.23 0.15 932SP* 157 136 119 105 93 0.68 0.59 0.52 0.46 0.40 924 102 89 69 53 35 0.44 0.39 0.30 0.23 0.15 934 102 89 69 53 35 0.44 0.39 0.30 0.23 0.15 934SP* 157 136 119 105 93 0.68 0.59 0.52 0.46 0.40 922 51 38 24 15 10 0.37 0.28 0.20 0.14 0.10 932 51 38 24 15 10 0.37 0.28 0.20 0.14 0.10 HEE Brushless motor 932SP 113 91 72 56 42 0.39 0.61 0.50 0.39 0.31 924 51 38 24 15 10 0.37 0.28 0.20 0.14 0.10 934 51 38 24 15 10 0.37 0.28 0.20 0.14 0.10 934SP 113 91 72 56 42 0.39 0.61 0.50 0.39 0.31
Note: Specifications given for a 230V power supply (+/-10%), 50Hz. For use at 60Hz, the input power and rotation speed values will generally be greater. * fan motor assembly not compliant with the ErP2015 Directive - Motor operating range: minimum return T°C: 0°C maximum return T°: 40°C
Name plate of the unit
The name plate contains all the information This plate is placed on the electrics box side. Code Serial number Description of the unit Rated motor output Motor rotation speed Coil type Wiring diagram reference Motor speed wiring Maximum service pressure Electric heater specifications (if fitted) required to identify the unit and its configuration.
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
349
COADIS LINE 900
4
Comfort units Coanda effect cassette