references
AQUAIR PREMIUM BCP
Air handling units for swimming pools
Electronic control Optimised energy consumption Scroll compressors and R-410A Plug-fan with EC HEE motor Heating and dehumidification of
covered pools
Dehumidification capacity:
56 to 74 kg water/h
410A
Dehumidification
Air filtration
Heating
Condensation heat recovery
Free cooling
Heat recovery
DESCRIPTION
are dehumidifi cation units by cooling circuit, with total condensing heat recovery, specially designed for conventional covered pools and other dehumidifi cation applications. These units have been designed for indoor or outdoor installation. For outdoor installation (optional), these units add a hood at the new air intake.
RANGE
AQUAIR PREMIUM BCP: 2 refrigerating circuits, 2 compressors, 2 models: 270 / 360
OPERATING
LIMITS
Condenser water inlet temperature Maximum: 50ºC Minimum: 20ºC
Air inlet dry temperature Maximum: 35ºC (65% RH - 29ºC WB) Minimum: 18ºC (90% RH - 17ºC WB)
PRINCIPLE
DIAGRAMS
EXTRACTION
Reversible coil C4 Evaporator coil (3 circuits) Return plug-fan C1 Condenser coil (2 circuits) Hot water coil Supply plug-fan
This unit consists of three stages of dehumidifi cation by means of three cooling circuits: One of the circuits condensates on a plates exchanger of SMO 254 steel, alloyed with chromium and molybdenum, with high resistance against corrosion in presence of chloride, filled with pool water, recovering part of the energy from the evaporation process. The other two circuits condensate on two air coils installed at the outlet of the evaporator, heating the cold and dry air that comes from it. It also integrates a cooling reversible circuit to recover the heat from the extraction air.
RETURN
SUPPLY
C2 Reversible coil
NEW AIR
C3
I
O
Plate exchanger
488