references
Split system Water chillers
DYNACIAT LGN
ELECTRICAL
CHARACTERISTICS
DYNACIAT LGN
120V
150V
200V
240V COMPRESSOR
300V
350V
400V
500V
540V
600V
Voltage Maximum rated current Starting current (1) Starting current with Soft Start option (1)
V A A A
23.2 137 70 30.2 174 60 42.2 139 76 46.2 160 93
400V - 3Ph - 50Hz (+10%/- 10%) 60.2 204 90 66.2 255 167 76 302 194 91.8 317.8 210 106.2 250 136 120.2 264 150
REMOTE CONTROL AUXILIARY CIRCUIT Voltage Maximum rated current Transformer capacity Electrics box protection rating Machine protection rating Breaking capacity Max. cable section according to disconnect switch (2) Max. cable section according to rating (3) DYNACIATPOWER LGN kA mm2 mm2
10 10 16 35 25 35
V A VA
230V - 1Ph - 50Hz (+10%/- 10%) Transformer fitted 0.4 100 IP 22 IP 22 50 70 50 0.6 160
700V
800V
900V
1000V
1100V
1200V
1400V
1600V
1800V
2100V
2400V
COMPRESSOR Voltage Maximum rated current Starting current (1) Starting current with Soft Start option (1) V A A A
140 316 230 160 334 248 182 391 287 205 414 310 400V - 3Ph - 50Hz (+10%/- 10%) 218 480 352 232 494 366 266 586 429 295 615 453 356 607 483 399 720 562 443 763 605
REMOTE CONTROL AUXILIARY CIRCUIT Voltage Maximum rated current Transformer capacity Electrics box protection rating Machine protection rating Breaking capacity Max. cable section according to disconnect switch (2) Max. cable section according to rating (3) kA mm2 mm2
95 120 40.5 240 185 240
V A VA
0.8 160
230V - 1Ph - 50Hz (+10%/- 10%) 1.3 250 IP 21 IP 21 61.5 70 300 2 x 185
(1) Starting current of largest compressor + maximum current of other compressors under full load (2) Max. cable section permitted by the disconnect switch in terms of cable diameter and connection terminals (3) Min. cable diameter required, determined from maximum rated currents.
170