Compact air-air rooftop units
PJ range
Natural or propane gas burner with modulating actuator, in accordance with the Gas Directive 2009/142/EC, installed inside a pre-assemby roofcurb (optionally supplied with the unit). Condensation boiler with premixing and modulation technology that allows outputs close to 109% with regard to the lower heating value (LHV).
PJ range 0090 to 0190 0200 to 0240 0280 to 0380 020 034 Model of PCH burner 045 065 080 080 105
The electronic control manages its connection, in heating mode, via an ON/OFF signal. On cooling-only units, the control activates the burner in the same way as an electrical heater stage. On heat pump units it is possible to select three different operating modes: • As a backup for the compressors as an electrical heater stage. • Instead of the compressors. • Instead of the compressors if the outdoor temperature is less than the value marked on an outdoor thermostat. The power control is carried out by the burner’s own control in accordance with the signal received from the unit control. Note: It is recommended to use the clogged filter detection and anti-freeze protection options for the components of the electrical cabinet when outdoor temperatures are low (compulsory if the outdoor temperature is lower than -10ºC WB).
Model Type of equipment PIN. NOx Class Range Thermal output (Hi) Useful thermal output Heater Performance kW kW % Hs Performance (H.C.V.) Flue losses with burner off (Hi) Flue losses with burner off (Hi) Losses in enclosure Max. condensation Exhaust gases Polluting emissions Carbon monoxide - C0 - (0% of O2) Nitrogen oxides - NOx - (0% of O2) Pa Power supply Power input Electrical Data Power input in stand-by Ingress protection rating Operating Temperatures (5) Connections Ø gas connection Ø intake/exhaust pipes GAS mm l/h ppm % % % Val
PCH020
PCH034
PCH045
PCH065
PCH080
PCH105
B23P - B53P - C13 - C43 - C53 - C63 - C83 0694CP1457 5 Min. 4.75 4.97 Max 19.00 18.18 Min. 7.60 8.13 Max 34.85 33.56 Min. 8.50 9.00 Max 44.00 42.40 Min. 12.40 13.40 Max 65.00 62.93 Min. 16.40 17.77 Max 82.00 80.03 Min. Max
18.00 100.00 19.63 97.15
104.63 95.68 106.97 96.30 105.88 96.37 108.06 96.82 108.35 97.60 109.06 97.15 94.26 0.4 86.20 4.3 96.37 0.6 86.76 3.7 95.39 0.5 87.36 3.7 <0.1 0% 0.4 0.9 1.1 <5 40 mg/kWh 22.28 ppm 80 41 mg/kWh 23.24 ppm 90 35 mg/kWh 19.84 ppm 100 230 Vac - 50 Hz 1-ph 12 45 11 74 24 82 <5 IP X5D -15°C to +40°C UNI/ISO 7/1- 3/4” 80/80 UNI/ISO 7/1- 1” 15 97 40 123 20 130 40 mg/kWh 22.68 ppm 34 mg/kWh 19.27 ppm 120 45 mg/kWh 25.51 ppm 2.1 3.3 2.7 97.36 0.2 87.22 3.2 97.62 0.3 87.93 2.4 98.25 0.2 87.52 2.8
Enclosure losses match those of the machine housing the PCH. Max. condensation produced acquired from testing 30%Qn. Value referenced to cat. H (G20) Weighted value to EN1020 ref. to class H (G20), referred to Hi (L.C.V.).