references
Water loop roof top unit
SPACE AQUA XF
High efficiency refrigerating circuits for R410A Refrigerating recovery option, adapted to air change requirements (EER and COP)
Assemblies with mixing boxes and free cooling management
Optional MO thermal and acoustic insulation
Indoor air quality achieved through unique combinations of gravimetric and opacimetric filters
Centrifugal fans or plug fan with EC motor
Comfort/heating options: electrical heaters, hot water coil, gas burner...
UNIT
COMPONENTS
Security features
High pressure switch. Low pressure switch. Compressor discharge temperature control. Check valve integrated into the compressor discharge. Main door switch. Thermal-magnetic protection for the compressor and fan motor power supply line. Automatic control circuit switch. Integrated anti-freeze protection in the control (heat pump units). Water flow controller (heat pump units) Condensation/evaporation three-way valve. pressure control: using a
Casing
Casing made of galvanised steel panels with polyester paint in RAL 7035 white. Thermal insulation, 10 mm thick, with M1 fire classification as standard. Free-standing frame and access panels for the electrical cabinet, compressors, fans, etc.
Outdoor circuit
Stainless steel welded plate heat exchangers.
Refrigerating circuit
Hermetic scroll compressors with acoustic insulation, fitted on anti-vibration mounts. Direction of rotation and phase balance control. Crankcase heater (heat pump units). Four-way reversing valve(s) (heat pump units). Liquid tanks. Acid-resistant dehumidifier filters.
Electrical cabinet
Complete electrical cabinet, fully wired. Insulated vertical unit cover to prevent condensation. IP55 protection. Mechanical ventilation controlled by the electrical cabinet to regulate the temperature and protect the components. Transformer for power supply without neutral. IP55 protection. Main earth connection. Compressor and fan motor switches.
Indoor circuit
Centrifugal belt-driven fan. Electric motor with tensioner, class F, IP55 and internal heat protection. One, two or three dual-inlet impellers with a wheel with forward-curved blades. Maintenance-free, lubricated ball socket. Reusable air filters, mounted on a frame. Coil comprising copper tubing and aluminium blades. Condensate drain pan. Thermostatic expansion valve with external equaliser.
552