references
Heat pump
ELECTRICAL
Power circuit Nominal voltage
SPECIFICATIONS
602C 650C 800C 900C 902C 1000C 1150C 1200C 1400C 1600C 1800C 2000C
Basic unit (excluding pump)
AQUACIATPOWER ILD ST
Nominal unit current draw(1) A Maximum unit power input(2) Unit Cosine Phi at maximum power (2) Maximum unit current draw (Un-10%)(3) A Maximum unit current draw (Un)(4) A A Maximum start-up current, standard unit (Un)(5) A Maximum start-up current, unit with soft starter (Un)(5) A
(1) (2) (3) (4) (5)
Conditions equivalent to the standardised Eurovent conditions (water type heat exchanger water input/output temperature = 12°C/7°C, outdoor air temperature = 35°C). Power input, compressors and fans, at the unit operating limits (saturated intake temperature 15°C, saturated condensing temperature 68.3°C) and nominal voltage of 400 V (data given on the unit name plate). Maximum unit operating current at maximum unit power input and 360 V. Maximum unit operating current at maximum unit power input and 400 V (values given on the unit name plate). Maximum instantaneous starting current at operating limits (maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor). Fan motor electrical data at Eurovent equivalent conditions and motor ambient air temperature of 50°C at 400 V: current 3.8 A, starting current 20 A, power input 1.75 kW
AQUACIATPOWER ILD HE Power circuit Nominal voltage
602C
650C
800C
900C
902C 1000C 1150C 1200C 1400C 1600C 1800C 2000C
Nominal unit current draw(1) A Maximum unit power input(2) Unit Cosine Phi at maximum power (2) Maximum unit current draw (Un-10%)(3) A Maximum unit current draw (Un)(4) A A Maximum start-up current, standard unit (Un)(5) A Maximum start-up current, unit with soft starter (Un)(5) A
(1) (2) (3) (4) (5)
Conditions equivalent to the standardised Eurovent conditions (water type heat exchanger water input/output temperature = 12°C/7°C, outdoor air temperature = 35°C). Power input, compressors and fans, at the unit operating limits (saturated intake temperature 15°C, saturated condensing temperature 68.3°C) and nominal voltage of 400 V (data given on the unit name plate). Maximum unit operating current at maximum unit power input and 360 V. Maximum unit operating current at maximum unit power input and 400 V (values given on the unit name plate). Maximum instantaneous starting current at operating limits (maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor). Fan motor electrical data reported upstream of the variable speed drive at Eurovent equivalent conditions and motor ambient air temperature of 50°C at 400 V: current 3.0 A; starting current 20 A; power input: 1.75 kW.
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
109
AQUACIATPOWER ILD