references
Water chillers Heat pumps
DYNACIAT ILG
HYDRAULIC
CONFIGURATION
Hydraulic module
This module is available for the entire DYNACIAT range.
Hydraulic module configuration
J K K
Features and options:
D
Expansion vessel Drain valve Buffer tank Air bleed valve Safety valve Hydraulic pump Options:
I
F
H
I
S E P
P
S
K
Kit for the flexible connections to the heat pump and indoor circuit Pressure gauge + control valve kit Screen filter Pump suction pressure safety device (option only available when the module is connected to a DYANCIAT LG or LGN)
E
D
J
R
F H R
Hydraulic module specifications
MHG Pump Max. power input Max. current at 50 Hz/400 V Min water flow rate Max. pressure Max water flow rate Min pressure Tank volume Expansion vessel volume Electrical supply Protection rating Hydraulic connections Dimensions Height x Length x Depth Weight Empty In operation
Ø mm kg kg No. kW A m3/h mWC m3/h mWC l l V
40
40 0.95 1.91 3 17.5 19 8.5
41
41 1.37 2.36 3 21.5 22.5 8
42
42 1.83 3.15 4 22 30 10 150 24 3 ph - 50 Hz - 400 V (+10%/-10%) + earth IP 55 1”1/2 - 2” - 2”1/2 1201 x 798 x 883 285 535
43
43 2.62 5.2 4 24.5 30 14
46
46 3.54 6 10 23 60 11.5
218
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A