references
Supervision for small installations
MAIN
FUNCTIONS AVAILABLE
Management of alarms:
The system's active alarms can be displayed. Different priority levels can be defined. Each alarm event which occurs in the installation is logged, giving information on the type of alarm, and the start and end time/date.
Remote control:
It is possible to monitor a PLANTWATCH PRO3 via an internet connection or a remote connection. This function allows exactly what is being displayed on the PLANTWATCH PRO3 touch screen to be shown on the PC monitor. The entire control of the installation can be programmed via the web.
Management of units:
All the units forming the installation can be quickly configured, by assigning them to defined groups or zones. All the information can be accessed via summary pages on the installation or detailed pages for each item of equipment.
Creation of diagrams:
PLANTWATCH PRO3 produces complete, detailed diagrams, with a maximum of 10 variables in each device. This is key for analysis and diagnostics in the event of a problem with the controlled variables.
Planner:
This is used to programme a series of actions according to the time/day.
TECHNICAL
DESCRIPTION OF
PLANTWATCH PRO
- Wall version • Touch screen 7’’ (800x480WVGA-65k colors) • 2 RS485 (Carel or Modbus protocol) • 1 USB Port (on the left side) • 1 SD Card Slot (for export and storing data) • 1 Network Card (2 Ethernet plug - SWITCH) • 1 Buzzer • Power supply 24Vac • 1 External Power Transformer: IN 110 240, OUT 24Vac • 2 Built in relay on board • 2 Status Led on the front (Alarms and Power status) • Ingress protection IP65 (front), IP20 (rear) • Mounting application: Technical room, office room - Panel version • Touch screen 7’’ (800x480WVGA-65k colors) • 2 RS485 (Carel or Modbus protocol) • 1 USB Port (on the left side) • 1 SD Card Slot (for export and storing data) • 1 Network Card (2 Ethernet plug - SWITCH) • 1 Buzzer • Power supply 24Vac • Ingress protection IP10 • Mounting application: e-box (electrical box), rack door, different technical enviroments
Software available in 14 languages: English remains the second language for support. CIAT machine variables available in 3 languages: Spanish, English and French. CIAT PLANTWATCH PRO supports Carel or ModBus protocols on RS485 bus. Supervision of CIAT controls: AVANT, AVANT+ and CIATrtc. Can be connected to a WM14-DIN electrical energy meter. The devices included in the system have a factory configuration for alarm priorities, recording frequency and the main page presentation. The units can be connected on 2 lines on the CIAT PLANTWATCH PRO3's two RS485 ports.
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
PLANTWATCH PRO3