references
Axial air heaters
HELIOTHERME 4000
HELIOTHERME PERFORMANCE - 230V/1PH/50HZ MOTOR - AC AND HEE
HEATING - 230V/1Ph/50Hz motor - AC and HEE
Model H4300 No. rows
2 1
Air supply speed SINGLE PHASE Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct
R3* R3* R3* R3* R3* R3* R3* R3* R3* R3* R3* R3* R3* R3* R3*
Flow rate m3/h 1 420 2 600 2 400 2 075 4 200 3 800 3 450 5 200 4 700 4 550 7 100 6 600 6 200 10 450 9 610 8 280
6 270 7 630 8 900 5 055 5 380 5 700 3 650 3 700 4 100 3 220 3 550 3 914 1 780 2 030 2 360
Air speed m/s 3.16 m/s 3.92 m/s 3.62 m/s 3.13 m/s 4.57 m/s 4.13 m/s 3.75 m/s 4.20 m/s 3.80 m/s 3.68 m/s 4.22 m/s 3.92 m/s 3.69 m/s 4.19 m/s 3.86 m/s 3.32 m/s
2.52 m/s 3.06 m/s 3.57 m/s 3.01 m/s 3.20 m/s 3.39 m/s 2.95 m/s 2.99 m/s 3.31 m/s 3.50 m/s 3.86 m/s 4.26 m/s 2.68 m/s 3.06 m/s 3.56 m/s
Heating capacity (kW) Wall- Suspended accelerator HPS mounted pump 15 3 35,87 40,57 22 6 32,07 36,92 Range (metres) 20 15 26 23 23 27 21 18 28 26 24 28 24 21
19 20 22 23 24 26 17 18 24 20 19 24 14 15 18
Sound pressure dB(A) 45 48 49 50
47 48 46
H4350
2 3 1
5 2,5 8,5
7,5 2 48,85 44,55 56,71 52,75 2,5
4
54 55 56 56 58 59
51 52 49 54 53 52
H4400
2 3 1
7 7
6 4 3 7 6
4,5
8,5 4,5 3,5 9 7 6,5 10,5 8,5 6,5
5 6 8 5,5 155,40 141 149,80 139 100,55 83,79 100 86,82
5,5
H4450
2 3 1
56 57 58 54 55 56
44 46 47 52 51 50
H4500
2 3 1
H4630
2 3
HEATING - COOLING - 230V/1Ph/50Hz Motor - AC and HEE
Model H4350 AC H4400 AC H4450 AC H4500 AC H4630 AC H4300 HEE H4350 HEE H4400 HEE H4450 HEE H4500 HEE H4630 HEE No. rows Air supply speed Air flow rate m3/h
1640 2160 3025 4060 1200 1640 2160 3025 4060 5960
Air speed m/s
2.47 m/s 2.35 m/s 2.44 m/s 2.41 m/s 2.67 m/s 2.47 m/s 2.35 m/s 2.44 m/s 2.41 m/s 2.39 m/s
Range (metres) Wall-mounted
23 26 24 23 12 23 26 24 23 21
Sound pressure dB(A)
30 48 45 54 43 30 48 45 54 53
3 2 3
Direct Direct Direct
ELECTRIC HEATING - 230V/1Ph/50Hz Motor - AC only
Model 4350 4400 4500 Air supply speed Direct Direct Direct Direct
R3* R3* R3* R3*
Flow rate m3/h 2600 4200 7100 7100
5700 5700 3914 2360
Air speed m/s 3.92 m/s 4.57 m/s 4.22 m/s 3.92 m/s
3.20 m/s 3.39 m/s 4.26 m/s 3.56 m/s
Range (metres) Wall-mounted 22 27 28 28
26 26 24 18
Electrical power (kW) Total 9.6 kW 18.9 kW 28.8 kW 43.2 kW No. of stages 2 2 2 3 Power per stage 2.4 kW 5.4 kW 10.8 kW
18 kW 13.5 kW 7.2 kW
Sound pressure dB(A) 48 54 56 56
50 50 52 46
14.4 kW x 3
Specifications determined using the following information:
Superheated water (HP SW): Temperature 180 - 120°C/RT=15°C – RH 50% Steam (HPS): Temperature 175°C - 8 bar/RT=15°C – RH 50% Air stream: * with JET+ diffuser for a residual speed of 0.1 m/s * defined with t OT/RT of 15°C (heating) and 7°C (cooling) * with LP water or electric heating Air speed: JET+ diffuser outlet Sound pressure: measured 5 metres from unit, directivity 2, attenuation of 22 dB Direct: speed obtained when wired directly to single-phase motor. R3* (version with AC motor): supply air speed obtained with autotransformer set to "3". Other operation points (5 in total) can be supplied on request by your agent using our technical selection software. 624
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A