references
QUICK
COP* SCOP s Prated Energy class
SELECTION
GeoCIAT Power 50H kW 12,48 4,15 4,45 % kW kW kW 170 12,4 A++ 12,02 3,31 11,9 2,95 3,32 % kW kW kW 125 11,4 A++ 16,50 5,31 15,85 4,22 230V - 1ph -50Hz -E+N dB(A) 54 54 50HT 12,16 4,24 4,56 175 12,3 A++ 11,55 3,33 11,8 3,03 3,43 129 11,3 A++ 16,39 5,42 15,74 4,25 65HT 15,80 4,21 4,5 172 15,8 A++ 15,08 3,30 14,8 2,93 3,31 124 14,4 A+ 21,13 5,32 20,03 4,15 400V - 3ph -50Hz -E+N 52 53 55 90HT 21,44 4,06 4,36 166 21,5 A++ 20,59 3,24 20,5 2,89 3,35 126 19,8 A++ 27,64 5,25 26,21 4,04 120HT 27.35 4.24 4.45 170 27.3 A++ 25.95 3.32 25.8 2.95 3.43 129 25.1 A++ 37.62 5.43 35.39 4.23
Heating capacity at 0/-3°C 30/35°C*
Heating capacity at 0/-3°C 40/45°C* COP* Heating capacity at 0/-3°C 47/55°C COP SCOP s Prated Energy class Heating capacity at 10/7°C 30/35°C COP Heating capacity at 10/7°C 40/45°C COP Power supply Sound power*
* Based on NFPAC conditions. Data certified by NFPAC under No. NF414-1384E/1278
WATER
FLOW RATES
IMPORTANT: The minimum flow rates must be observed. If they are not, the exchanger may be damaged by frost. CIAT shall not be held liable for frost which results from flow rates below the minimum flow rates stated above. The nominal flow rates are used to size the hydraulic system.
GeoCIAT Power Outdoor heat exchanger
3/h) 3/h) (1) 3/h) (2) 3/h)
50H(T) 1,45 2,9 3,9 1,1
3/h) (1) 3/h) (2)
65HT 1,85 3,7 4,9 1,35 2,7 3,7
90HT 2,45 4,9 6,7 1,8 3,6 4,9
120HT 3,2 6,4 8,7 2,35 4,7 6,4
Indoor heat exchanger
2,2 2,9
(1) Heating mode, underground loop, indoor 30/35°C, outdoor 0°C/-3°C (2) Heating mode with ground water, indoor 30°C/35°C, outdoor 10°C/7°C
HYDRAULIC
CONNECTIONS
System pipe diameters calculated for a hydraulic connection for your machine of 15 m between the unit and the rest of the system.
GeoCIAT Power 50H(T) 65HT 90HT 120HT
Connection diameter 1’’1/4 G male 1’’1/2 G male
Copper pipe hydraulic con- Steel pipe hydraulic connecPE pipe hydraulic connection nection tion 36x1 38x1 54x1 40/49 - DN40 1’’1/2 50/60 - DN50 2’’ 40x3.7 50x4.6 63x5.8
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
209
GeoCIAT™ Power
2
Heat pump Heating only, Glycol/water mix