references
Humidity Temperature Thermal and acoustic insulation (50 mm thick), with Euroclass A2-s1, d0 (M0) fire classification. Casing losses:
Conditions Indoor Outdoor 9 mm NBR (std) 50 mm mineral wool Conditions Indoor Outdoor 9 mm NBR (std) 50 mm mineral wool Winter 20ºC -20ºC 50% RH 94% RH
Droplet eliminator on the indoor air coil. Recommended if high levels of air humidity are expected or when the air flow rate is high. Droplet eliminator on the outdoor air intake. Tropicalised components on the electric panel with protective varnish: control board, card and terminals. Tropicalised fans and motors (please contact us).
Indoor separator
1790 W 2.0% HC 437 W 0.4% HC
Summer 27ºC 35ºC 50% RH 40% RH
615 W 1.00% HC 151 W 0.24% HC
Electrical heaters to protect the components of the electrical cabinet. Compulsory if the outdoor temperature is below -8ºC WB. For temperatures below -16ºC WB, a reinforced heater will be compulsory. Compressor with protection against low temperatures (additional crankcase heater): required if the outdoor temperature is below -8ºC WB. Dampers with springs for automatic closure in the case of a power outage. Electrical heater for antifreeze protection for the mixing box dampers: required if the outdoor temperature is below -12ºC WB. Hot water coil circuit with antifreeze protection according to the water temperature: required if the outdoor temperature is below -20ºC WB (includes an accelerator pump). Corrosion Coils (outdoor, indoor and/or auxiliary) with copper tubes and copper blades. INERA® coils (outdoor, indoor and/or auxiliary) made from copper tubing and aluminium alloy blades, exclusive to CIAT, highly efficient and extremely resistant to corrosion. Coils (outdoor indoor and/or auxiliary) made from copper tubing and aluminium blades, with polyurethane coating, or a coil with full Blygold protection. Condensate drain pan in stainless steel for the indoor circuit.
Hot water auxiliary coil, with three-way valve. This optional always incorporates an anti-freeze thermostat as safety system. Consult for percentages of glycol water above 20%. Auxiliary electrical heaters, with two power stages and on/off control, for assembly and connection inside the unit. Electrical support is not available in models 90 to 180 with top supply and centrifugal fan (optional). Note: the differential pressostat for control of air flow is included with centrifugal fan (optional). Natural or propane gas burner with modulating actuator. Available for all assemblies except top and bottom supply outlet. With this option, it is recommended to have the differential pressostat option for detecting clogged filters. Note: with centrifugal fan (optional), it is compulsory the differential pressostat for controlling the air flow that stops the burner in case of fire. Note: a protection kit of low temperature is available for an outdoor temperature lower than -15ºC.
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
517
SPACE PF 90 - 360
Roof top