references
Water loop roof top unit
Scroll compressors R-410A refrigerant Flexible configuration Silent operation Plug-fan with EC HEE motor (optional)
Cooling capacity: Heating capacity:
107 to 183 kW 122 to 227 kW
410A
Cooling only
Cooling and heating
Free cooling
Air filtration
Motor
DESCRIPTION
Roof top SPACE AQUA XF units are compact packaged horizontal self-contained water-to-air units, operating on a water loop. They are equipped with centrifugal fans, plate heat exchangers, hermetic scroll compressors and an electronic control with a microprocessor, all components optimised to run with R410A refrigerant. These units are designed to air condition large commercial or industrial spaces. They are easy to install and offer reliable operation. The broad range of options means that most operating requirements can be met. All the machines contain a refrigerant load. They are tested in the factory to check that all the components are operating correctly.
SERIES
SPACE AQUA RXF series Compact horizontal roof top water-to-air refrigeration unit. SPACE AQUA IXF series Compact horizontal reversible water-to-air roof top heat pump unit.
RANGE
RXF - IXF series: 2 refrigerating circuits, 2 compressors, 6 models: 415 / 420 / 480 / 485 / 540 / 600 RXF - IXF series: 2 refrigerating circuits, 4 compressors, 2 models: 650 / 720
OPERATING
Conditions Air inlet Water
LIMITS
Refrigeration 14ºC WB 22ºC WB 5ºC (1) (3) 55ºC (1) Heating 10ºC 27ºC 5ºC (2) (3) 35ºC (2)
(1) Water outlet temperature. (2) Water inlet temperature. (3) If there is a risk that the plate heat exchangers may freeze, it will be necessary to use water.
Minimum Maximum Minimum Maximum
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
551
SPACE AQUA XF