references
Air-to-water heat exchange coils
from 500 to 5000 m3/h
USE
Coils designed for heating or cooling air by circulating a hot or cold fluid inside the tubes, most commonly water or a glycol/ water mix. The air can also be used as a heating or cooling source. These coils can be installed in a duct.
RANGE
Range of low profile coils, available in 5 different lengths.
DESCRIPTION
Finned bundle with: - 2 rows of copper tubes, ø 3/8" (9.52 mm) or ø 1/2" (12.7 mm), according to the model, - aluminium blades at 1.6 mm intervals. Connection using tapped couplings with an air bleed valve. Galvanised steel frame - Tightness: none Limits of use: Maximum Permissible Pressure (PS) = 15 bar eff. 110°C. Each coil is air-tested underwater. Equipment classified as Art.4.3 as per Directive 2014/68/UE.
CHARACTERISTICS - DIMENSIONS
11,5 4,5 11,5 4,5
4 holes, Ø4.2 (on each face)
57,5
39
23
192
256
39
270
7
108,5
Supply piping Ø J Horizontal Air Flow Operation Positions D090 Piping to the right
BCV A B C D ØJ Tubes Nc* Fa (m2)** Capacity dm3 Empty weight (kg) Transfer area m2
325 323 300 314 13,5 3/8" 9,52 1 0,077 0,40 1,9 5
327 473 450 464 13,5 3/8" 9,52 2 0,12 0,57 3,25 7,44
329 673 650 664 13,5 3/8" 9,52 2 0,17 0,78 4,7 10,7
331 873 850 864 15 1/2" 12,7 2 0,22 1,8 6,7 13,2
333 1073 1050 1064 15 1/2" 12,7 2 0,27 2,2 8,2 16,3
G090 Piping to the left
* Nc: no of circuits ** Fa: face area
23
224
HEAT PUMPS - AIR CONDITIONING - COOLING - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A
317
BCV
3
Compact Low profile