references
Heat pumps and gas boilers
AQUACIAT2HYBRID
ELECTRICAL
CHARACTERISTICS
ILDC-ILDH basic unit (excluding pump and gas module)
AQUACIAT2HYBRID Power supply Monitor circuit voltage Starting current (excluding pump) Starting current, SOFT START option TN-TT neutral system breaking capacity Max. wire cross-section Max. nominal current ILDC- ILDH (1)
(1) Pump current not included
180V ph/Hz/V ph/Hz/V A A kA mm2 A 129 70 15 35 40
200V
240V
300V
3~50Hz 400V (+10%/-10%) + Earth
139 76 15 70 47
160 93 15 70 52
205 91 10 70 68
Gas module (MG) only
AQUACIAT2HYBRID Power supply Max./min. power input ph/Hz/V W 198/151 MG 50 MG 65 1~50Hz 230V (+10%/-10%) + Earth 228/156 297/168 MG 85
HYDRAULIC
CONFIGURATIONS
AQUACIAT2HYBRID reversible air-to-water heat pumps are available in 2 versions: - Hydraulic unit equipped with a single or dual pump: AQUACIAT2HYBRID ILDC - Hydraulic unit equipped with a single or dual pump and buffer capacity: AQUACIAT2HYBRID ILDH
AQUACIAT2HYBRID 180V – 300V models
"C" versions ILDC - MG "H" versions ILDH - MG
Aquaciat2
GAS module
Aquaciat2
HM tank
GAS module
300
2-TUBE MODULE Basic version With 1 or 2 single internal pumps no. 40 to 41 GAS module
2-TUBE MODULE Basic version With 1 or 2 single internal pumps no. 40 to 41 HM tank GAS module
180
Aquaciat2
Aquaciat2
4-TUBE MODULE DHW option with GAS With 4-tube option for DHW pre-heating
4-TUBE MODULE DHW option with GAS With 4-tube option for DHW pre-heating
60
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 17.01 A